263
this post was submitted on 25 May 2024
263 points (93.7% liked)
Technology
59374 readers
3392 users here now
This is a most excellent place for technology news and articles.
Our Rules
- Follow the lemmy.world rules.
- Only tech related content.
- Be excellent to each another!
- Mod approved content bots can post up to 10 articles per day.
- Threads asking for personal tech support may be deleted.
- Politics threads may be removed.
- No memes allowed as posts, OK to post as comments.
- Only approved bots from the list below, to ask if your bot can be added please contact us.
- Check for duplicates before posting, duplicates may be removed
Approved Bots
founded 1 year ago
MODERATORS
you are viewing a single comment's thread
view the rest of the comments
view the rest of the comments
What's wrong with that? That's how basically any balcony solar system works.
The cables in your walls are designed for a certain maximum current before they start to heat up. This current is limited by your breaker.
Now if you introduce a plug in solar setup your current is limited by your maximum breaker capacity + whatever your solar setup can generate.
So if I'd use the specs from the article and apply it to a normal dutch home situation: 16A breaker, + 800W at 230V, which means ~3.5A = 19.5A max. which is probably still fine for short durations.
But now some genius doesn't read the fine print and hooks up 2 or 3 on the same circuit. There is no electrician that tells him that's dangerous because it's all self installed and he doesn't know any better. And all of a sudden you are up to 26.5A and you got glowing, smoking wires in your walls...
Your breaker will pop. Just like if you were to run a hair dryer on each outlet.
The breaker only sees the current flowing through the breaker though. Not the additional current provided by the solar panels since those don't flow through the breaker. So it will pop later then that the cables are rated for, therefore introducing an overheat and fire hazard.
Maybe for a same-circuit device that’s consuming more than the breaker can provide? I don’t know enough about this tech but would expect this can be accounted for in some way.
There are ways to somewhat fix it for circuits with a single use.
Fixing the same example: A 16A breaker for the solar feed in, a single 16A breaker for all the consuming appliances on that circuit. And another 16A breaker on the feed in for that circuit is an example that is sometimes used in the Netherlands to add a feed in to an existing circuit with a single outlet connected to it. Meant for washingmachines for instance.
This ensures that the circuit on all circumstances has a maximum current of 16A flowing over any wire by also measuring the outgoing current of both feed in circuits. But if you have multiple outlets you'd still need to stiol measure at a single place or use low enough breakers per outlet that the total stays below the 16A. Which the UK might have if I recall correctly.
Then again this is not a normal setup and requires change in the electric circuit of the home. Which most consumers won't even realize. Like I said, if everyone keeps to the fine print this thing probably has and limits the extra plug-in solar panels to 1 per circuit, it's unlikely to actually cause issues because of overdimensioning of the wires. And the safety margin built in which is likely how they have gotten approval. But ignoring or not reading that text and plugging multiple in on the same circuit can and will cause a fire hazard with heavy consumers on the same circuit.